Product Features:

  • Measuring range: 1-9999.9µΩ The highest resolution: 0.1µΩ

  • Measuring current: DC 100A

  • Measurement accuracy: 0.5%±2 words

  • Display mode: large-screen LCD with Chinese characters

  • Power supply: AC220V 50Hz

  • Maximum output voltage: DC 5V

  • The instrument has accurate measurement, stable performance and easy operation. It is suitable for the requirements of on-site high-voltage switch maintenance and loop resistance testing of high-voltage switch factories in electric power and power supply departments.

  • Test time setting range: 10-30-60S

Product nicknames: contact resistance tester, switch loop resistance tester, contact loop resistance tester, resistance loop tester, intelligent loop resistance tester, contact resistance tester, contact (loop) resistance tester.

In the past, the conventional QJ44 double-arm DC bridge was generally used in the power system to measure the DC resistance of the transformer coil and the contact resistance of the high-voltage circuit breaker. The test current of this type of bridge is only mA level, and it is difficult to find the conductive loop conductor of the transformer coil Defects of reduced area. When measuring the contact resistance of the conductive circuit of a high-voltage switch, due to the influence of the oil film and the oxide layer between the moving and static contacts, the measurement deviation is large, which conceals the true contact resistance.

Therefore, the Ministry of Electric Power standard SD301-88 “AC 500KV Electrical Equipment Handover and Preventive Test Regulations” and the new version of the “Electrical Equipment Preventive Test Regulations” stipulate that the measuring current of the contact resistance of circuit breakers and disconnectors shall not be less than DC 100A to ensure Accuracy.

The loop resistance tester is controlled by a miniature single-chip microcomputer and displayed on a humanized Chinese character interface. It is a special device for measuring contact resistance and loop resistance of switch control equipment; its test current adopts 100A DC recommended by the national standard GB763, and the loop resistance is directly measured Or contact resistance, the first test time setting!!!, the first test automatic identification of large current disconnection

Measuring range1~1999μΩ
Resolution1μΩ
Test currentDC 0-100A continuously adjustable
measurement accuracy0.5%±1d
Display methodCurrent: Three and a half LCD
Resistance: Three and a half LCD
Power supplyAC220V±10% 50Hz
working environmentTemperature -10℃~40℃, humidity: ≤80%RH
Volume300×270×200 mm3
Weight5Kg (without accessories)