Project Description

Product Features:

  • Automatic collection, measurement, display, storage and printing of all measurement parameters and impedance characteristic curves (voltage, current, impedance, power, frequency, equipment number, time, etc.).

  • Automatically collect the real-time speed of the generator (requires the support of the speed sensor), and can measure the rotor AC impedance and its characteristic curve of various synchronous generators in dynamic and static conditions.

  • Super long range, can measure all generator rotor AC impedance and characteristic curve automatically and manually.

  • Comes with a miniature printer, which can print AC impedance test reports and AC impedance characteristic curves in real time.It can also be used for no-load and short-circuit tests of single-phase transformers.

The generator rotor AC impedance tester is a special instrument for judging whether the generator rotor winding has an inter-turn short circuit. It also ac impedance test generator rotor. It can measure the voltage, current, impedance, power, speed and other parameters of the rotor winding automatically and manually (one-way or two-way).

LTFZ generator rotor AC impedance tester adopts advanced high-speed microprocessor technology, which is more powerful, superior in performance, and more convenient to use. It has the characteristics of high reliability, easy operation, high test accuracy, compactness and lightness. At present, it is at the leading level in the country.

Built-in large-capacity memory, can store test data, and upload to PC via standard industrial communication interface (RS232), use the random software developed by our company to realize data download, automatically generate and edit typical test reports, which is convenient for technical management and archiving .

It has perfect over-voltage and over-current protection functions, in which the over-current and over-voltage protection value is automatically adjusted according to the setting of the test parameters, which is simple and can ensure the safety of the equipment under test.

Main technical indicators of generator rotor AC impedance tester

1. Environmental conditions

Temperature: -5°C~40°C

Relative humidity: <95% (25°C) Altitude: <2500m

External interference: no strong vibration, no strong electromagnetic field Power supply: 185VAC~250VAC, 45Hz~65Hz

2. Performance indicators

AC impedance 0-1Ω0.2%FS±2 words 
1-6000Ω0.20%
AC voltage0-50V0.2%FS±2words
Alternating current50—600V0.20%
0—10A0.2%FS±2 words
10A—120A0.20%
Active power0—1kW0.1>CosΦ>01%FS±2 words
When Cos Φ>0.10.5%FS±2 words
1kW—72KW0.1>CosΦ>01%FS±2 words
When CosΦ>0.10.5%FS±2 words
Frequency40---75HZ0.20%
Volume415×225×200mm
weight5kg

3. Insulation strength
1. The insulation resistance of the voltage and current input terminals to the chassis is ≥100MΩ.

2. The power frequency is 2KV (effective value) between the input end of the working power supply and the shell, and the experiment lasted 1 minute.