Project Description
Product Features:
Online monitoring function: when the battery pack is in the state of online discharge, equalization and floating charge, the battery pack and each single cell can be monitored online in real time. The monitoring content includes: the entire battery pack voltage, each single cell Indicators such as voltage, battery pack charging and discharging current, battery pack monitoring time, and battery pack charging and discharging capacity.
The device supports constant current and constant power discharge test modes: it can meet a variety of test requirements. When the battery capacity needs to be tested, the constant current discharge mode can be selected to accurately test the actual capacity of the battery pack; when the battery load capacity needs to be tested, you can Select the constant power test mode to accurately simulate the backup power supply time of the battery pack with real load.
The 220V380V battery discharge test series is a special instrument for testing UPS battery packs, with functions such as “online monitoring” and “checking discharge” for battery packs.
The equipment adopts the current advanced testing technology principles, and has made a series of breakthroughs in the research and application of new technologies, new devices, new materials, and new processes. It is designed in accordance with the requirements of relevant national testing and maintenance regulations to perform performance testing on batteries. Professional testing equipment.
The instrument has large discharge power, small size, light weight, and complete functions of the upper computer data management software, which greatly reduces the workload of daily battery testing and maintenance.
Online compensation discharge function: during online discharge, the host display current = battery pack discharge current = host internal dummy load current + actual load current, since the actual load current will change with the online voltage during online discharge, the host internal dummy load The battery will also be adjusted automatically to ensure that the battery pack is always discharged in a true constant current mode
Special | Technical Parameters |
---|---|
Type number | 220V380V/03 |
Cell voltage measurement type | 1.2V/2V/6V/12V |
Single voltage measurement range | 2V:0~4V 6V:0~8V 12V:0~15V |
Cell voltage resolution | 2V/6V: 0.001V 12V: 0.01V |
The whole set of voltage measurement range | 0~450V |
Whole group voltage resolution | 0.01V |
Voltage test accuracy | 0.50% |
Discharge current working range | 2~30A can be set continuously. |
Constant current discharge voltage range | 170-440V |
Discharge current control accuracy | 0.1A |
Current test accuracy | 1% |
Operating Voltage | AC 220V±15% |
Cooling method | Strong air cooling |
communication method | RS232 communication and SD card port communication |
Display method | 7-inch color LCD display with touch |
weight | Less than 40Kg |