Project Description
Product Features:
System insulation resistance measurement function, the instrument can measure the system’s positive-to-ground insulation resistance and negative-to-ground insulation resistance, which can achieve 0-999.9KΩ measurement;
AC channel current detection function, the instrument can judge the AC channel current failure in the DC system, and can measure the AC voltage value in the DC system, the AC voltage measurement range is 0-280V;
Insulation index analysis function. When using the grounding function to detect, after detecting a branch, the detector will display the insulation index of the branch for the user’s reference and analysis
“Analyzer” and “Detector” both use LCD screens for users to view information
In order to help on-site maintenance personnel to quickly and accurately find the ground fault point, our company has developed a portable DC ground fault finder through years of hard work and summed up a large amount of field experience. It also call ground fault indicator. This finder can find and solve various voltage levels (48V, 110V, 220V) Insulation faults such as indirect grounding, non-metal grounding, loop grounding, simultaneous positive and negative grounding, positive and negative balance grounding, AC and DC channeling faults, and multi-point grounding in the DC system.
The portable DC ground fault finder adopts a high-resolution sensor unit to collect the leakage current of the grounding point in the DC system, and detects the insulation resistance to the ground within 600KΩ under the 220V voltage level. The detection speed is fast and the positioning is accurate, which truly solves the DC problem. Insulation failure in the system.
Ammeter function, the device can be used as a high-precision ammeter, and the current measurement resolution can reach 0.01mA;
It has a non-signal grounding search function, and the device can locate the ground fault point without injecting any signal into the system;
Direction display function. For branch circuits with grounding indications tested, the instrument will have direction indication arrows to remind the user of the relative direction between the grounding point and the grounding point being searched, which improves the search efficiency.
Insulation index analysis function. When using the grounding function to detect, after detecting a branch, the detector will display the insulation index of the branch for the user’s reference and analysis.
Main technical indicators of DC ground fault finder | |
---|---|
(1) Use environment | |
Ambient temperature: | -30℃~+50℃; |
Relative humidity: | ≤95%; |
(2) Technical indicators of wireless communication | |
Signal power: | ≤ 10dbm; |
Signal frequency band: | 433Mhz; |
Sensitivity: | -106dBm; |
Transmission distance | In the case of line-of-sight, the reliable transmission distance of 2 meters above the ground is 250 meters |
(3) Analyzer technical indicators | |
Applicable DC system voltage level: | |
System positive and negative voltage measurement range: 0—300V | 48V, 110V, 220V or user specified voltage level |
Measurement range of DC voltage to ground: | 0—300V |
Measurement range of AC voltage to ground: | 0—280V |
Alarm threshold for AC channeling fault: | 5V |
Voltage measurement resolution: | 0.1V |
Measuring range of system resistance to ground: | 0—999.9KΩ |
Ground resistance measurement resolution: | 0.1KΩ |
Display method: | LCD |
Detection signal current size: | 0-2mA adjustable |
Detection signal voltage amplitude: | 0-50V adjustable |
Signal frequency: | No signal mode and 0.16Hz optional |
Anti-DC system distributed capacitance interference: | 1000uF |
(4) Detector technical indicators | |
Detection range of branch insulation resistance in signal mode: | |
The system voltage level is 220V: | 0 -600KΩ |
The system voltage level is 110V: | 0 -300KΩ |
The system voltage level is 48V: | 0 -60KΩ |
Insulation resistance measurement resolution: | 0.1KΩ |
Detection range of branch insulation resistance in no signal mode: | |
The system voltage level is 220V: | 0 -50KΩ |
The system voltage level is 110V: | 0 -25KΩ |
The system voltage level is 48V: | 0 -10KΩ |
Insulation resistance measurement resolution: | 0.1KΩ |
Waveform display time: | 12 seconds |
Current measurement range: | ±100mA |
Current measurement resolution: | 0.01mA |
Display method: | LCD |
Direction display mode: | Same direction or reverse marking |
Anti-DC system branch circuit distributed capacitance interference: | 100uF |
Use distance between analyzer: | No distance limit |
Jaw size: Ф30mm | Ф30mm |
Packing List | |
---|---|
1. Analyzer | 1 set |
2. detector | 1 set (with collector) |
3. double A battery | 4 knots |
4. charger | 1 piece |
5. Three-core cable | 1 |
6. Manual | 1 copy |
7. Certificate of conformity | 1 serving |
8. Warranty Card | 1 serving |
9. suitcase | 1 piece |