Project Description

Product Features:

  • The 1000A DC circuit breaker ampere-second characteristic tester can be used alone or online with a PC

  • 320×240 liquid crystal display, high-speed thermal printer, man-machine dialogue and full keyboard operation mode, intelligent work in the whole process

  • The DC circuit breaker ampere-second characteristic tester uses power electronic control technology to generate large current output, with fast response speed, high accuracy and continuous adjustment

  • Multiple high-precision sensors automatically switch the current range and high-performance 14-bit AD acquisition chip

  • The DC circuit breaker ampere-second characteristic tester has a power-down storage function and can store 200 sets of test data

Product aliases: DC circuit breaker ampere-second characteristic tester, ampere-second characteristic, DC circuit breaker ampere-second characteristic tester, 1000A DC circuit breaker ampere-second characteristic tester, DC circuit breaker ampere-second characteristic tester, DC circuit breaker ampere-second tester Tester, DC circuit breaker characteristic tester, DC switch ampere-second characteristic tester, circuit breaker ampere-second characteristic tester, DC circuit breaker tester, ampere-second characteristic tester, circuit breaker ampere-second tester. It belongs to a kind of circuit breaker tester.

Suitable for the ampere-second characteristic test of rated current 1A~1000A DC circuit breaker and 6A~100A DC fuse

Standard support: DL/T352-2010, GB10963.2-2008, GB/T11022-2011

1000A ampere-second characteristic tester adopts 320×240 liquid crystal display

DC circuit breaker ampere-second characteristic tester adopts power electronic control technology to generate large current output

Tester modelDAS-1000A
Tester nameDC circuit breaker ampere-second characteristic tester·1000A DC circuit breaker ampere-second characteristic tester
power input220V±10%, frequency: 50Hz±0.5 Hz;
Test current range0—1000A
Test current ripple coefficient<2%;
Stability of output current≤0.5%
Ampere Action TestTime record: 0-9.9S;
Minimum time resolution: 0.1mS
No-flow testTime record: 0-9999S
Minimum time resolution: 0.1S;
Ambient temperature-20°C to 50°C
Dimensions560mm(length)×410mm(width)×350mm(height)
weight31kg
Fill out my online form.