Configuration scheme of  high voltage detector equipment

Test itemTest equipmentTechnical indexReference
Insulation resistance measurementAnalog megohmmeter Digital megohmmeter500~2500V 10000MΩShort circuit current is not less than 2mA
DC withstand voltage and DC leakage measurementDC voltage generator200kV 2mARipple coefficient is not more than 1%
Power frequency high voltage test deviceConsole, voltage regulator, test transformer25kVA/150kVWaveform distortion is less than 5%
Transformer DC resistance measurementTransformer DC Resistance Tester≥1A 1mΩ~200Ω 0.2 level
Transformer ratio measurementTransformer testerMeasuring range: 1~100 accuracy: 0.2 level
Transformer empty short circuit testTransformer comprehensive test deviceMeasurement accuracy is not less than 0.5 level
Conductive circuit contact resistance measurementLoop resistance testerAccuracy: 0.5 grade 1µΩ~2mΩThe output current is not less than 100A
High-voltage switch mechanical action characteristic measurementHigh-voltage switch comprehensive testerAccuracy: ±0.1%
Insulating oil dielectric strength testInsulating oil pressure deviceVoltage measurement accuracy: Class 3.0Steady state measurement accuracy: 1.5 level
Vacuum switch fracture withstand voltage testVacuum testerMeasuring range: 0.1~0.00001
Test voltage measurementHigh voltage divider measuring systemAccuracy: AC1.0 level DC0.5 level
Dielectric loss and capacitance measurementHigh voltage bridge or dielectric loss measuring instrumenttgδ: ±5% Electric capacity: ±%
Ground resistance measurementGround Resistance TesterOutput current: 1A accuracy: ±5%The interference current of the fundamental wave does not exceed 50mA
Measuring range: 0~1999mA
Micro current measurementDC microammeterResolution: 1mA
Micro current measurementAutomatic or remote control shift DC microammeter0~2000µA accuracy: 0.5 level
Infrared temperature measurementThermal imaging cameraSensitivity: 0.1℃Recommended configuration
Infrared temperature measurementPoint thermometerAccuracy: 1%Recommended configuration
Time measurement range: 0~250ms accuracy: ±0.1%
Transformer on-load tapping switch testOn-load voltage regulator switch testerResistance measurement range: 0.1~20Ω accuracy: ±1.0%
Resistance measurement of zinc oxide arresterZinc oxide arrester tester0~20mA
Setting protection setting value measurementMicrocomputer protection testerSix currents, six voltages
Grounding resistance measurement of grounding gridGround network continuity testerRange: 0.1mΩ~5Ω
Input: 220V Output: 500V
CT/PT characteristic testTransformer comprehensive characteristic testerInput: 380V Output: 1000V
Inspection range: 0.09Mpa
Density relay measurementSf6 density relay automatic calibratorInspection accuracy: 1.0 level
Lightning counter measurementLightning counter action measuring instrumentOutput voltage: 800~1000V
Withstand voltage test of electrical equipmentFM series resonance test deviceWeight: 780g